Trane Furnace 3 flashes

What this problem usually means

Trane uses this flash count on two different control families, so note which LED is flashing (red LED = single-stage control; green LED = two-stage control). On single-stage furnaces (XR80, XR90, XR95, XB80, XB90 families) with the integrated furnace control (IFC), 3 flashes means a pressure switch fault — the draft pressure switch did not prove proper inducer draft as expected. On two-stage furnaces (XV80, XV90, XV95, XL80, XL90 families, *UD2/*DD2), 3 flashes means the first-stage pressure switch is stuck open or there is an inducer error — draft was not proved for first-stage heat.

Likely causes

  1. Blocked or frozen vent or intake termination
  2. Clogged or frozen condensate drain or trap
  3. Weak or failed inducer motor
  4. Failed pressure switch (the first-stage switch on two-stage models) or cracked pressure hose

How to fix it — step by step

  1. Check the outdoor PVC intake and exhaust terminations and clear snow, ice, leaves or debris you can safely reach
  2. Check the condensate drain hose and trap for kinks, clogs or freezing
  3. Confirm the thermostat is calling for heat and the furnace switch is on
  4. Reset power once (off 30 seconds, then on) and watch whether the code returns
  5. If it returns, call a technician to test the inducer, pressure switch and venting — do not bypass the switch

Parts that commonly fix it

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.