Carrier Furnace 34 Error Code

What the 34 code means

Ignition proving failure. On Carrier 58-series furnaces, code 34 means flame was not sensed during the trial for ignition; the control retries three more times before going to ignition lockout code 14.

Likely causes

  1. Oxide buildup on the flame sensor
  2. Defective hot surface igniter
  3. Gas valve defective or turned off, or manual shutoff closed
  4. Low inlet gas pressure
  5. Poor control ground continuity

How to fix it — step by step

  1. Confirm other gas appliances work, so you know gas service is on
  2. Make sure the manual gas shutoff near the furnace is open
  3. Make sure the furnace access doors are fully closed
  4. Cycle power once at the service switch for one clean retry
  5. If 34 repeats or becomes 14, call a technician - cleaning the flame sensor and testing the igniter are done inside a live gas appliance

Parts that commonly fix the 34 code

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Related Carrier furnace error codes

See all Carrier furnace codes & guides →